COMPARISON OF COOLING LOAD CALCULATION METHODS BY

Authors

  • Prof. Dr. Khalid A. Joudi Department of Mechanical Eng., Baghdad University, Iraq

Abstract

Abstract

The present work includes cooling load measurement in Iraq. One room located in Baqubah was the object of the study. The measurement was taken for the room in summer months of 2004 (i.e. in May, June, July, August & September). The area of test room was 15 m2 and 3 m ceiling height with medium weight construction specifications. The test room includes exterior east and west wall facing, un-conditioning adjacent space with an exterior roof, east window and an exterior west door. The air conditioner unit used in this work was a window type with a nominal capacity of 2 T.R. (7 kW). The theoretical cooling load was predicted by three methods of cooling load calculation, which are TFM, CLTD/SCL/CLF & TETD/TA methods. Measurement of cooling load showed that there is a large difference between the measured and predicted cooling load with all theoretical methods. The difference ranged from 33% to 40%. This large difference is appear because of the several season such as the air conditioner type, suffer environmental and the construction specification of the test room where it’s represent the Iraqi building and not exactly same as building specification tabulated in ASHRAE tables

References

REFRENCES

ASHRAE Handbook - Fundamentals, American Society for Heating,

Refrigeration and Air Condition Engineers, Inc., New York

(1967).

ASHRAE Handbook - Fundamentals, American Society for Heating,

Refrigeration and Air Condition Engineers, Inc., New York

(1972).

ASHRAE Handbook - Fundamentals, American Society for Heating,

Refrigeration and Air Condition Engineers, Inc., New

York (1977).

ASHRAE “Cooling and Heating Load Calculation Manual”

American Society for Heating, Refrigeration and Air

Condition Engineers, Inc., New York (1979).

ASHRAE Handbook - Fundamentals, American Society for Heating,

Refrigeration and Air Condition Engineers, Inc., New York

(1981).

ASHRAE Handbook - Fundamentals, American Society for Heating,

Refrigeration and Air Condition Engineers, Inc., New York

(1997).

McQuiston, F. C. & Harris, S. M., “A study to categorize walls and

roofs on the basis of thermal response”, ASHRAE

Transactions, 94(2), 688 – 715 (1988).

Mitalas, G. P., & Stephenson, D. G. “Room Thermal Response

Factors”, ASHRAE Transactions, 73(II), III.2.1 - 2.10

(1967).

Mitalas, G. P., & Stephenson, D. G. “Calculation of heat conduction

transfer functions for multi - layer slabs”, ASHRAE

Transactions, 77(2), 117 – 126 (1971).

Romine, T. B. (Jr.). “Cooling Load Calculation”: Art or Science,

ASHRAE Journal, 34, 14 – 24 (1992).

Rudoy, W., & Duran, F. “Development of an Improved Cooling Load

Calculation Method”, ASHRAE Transactions, 81(2), 19 – 69

(1975).

Sowell, E. F., & Chiles, D. C. “Characterization of zone dynamic

response for CLF / CLTD tables”, ASHRAE Transactions,

(2A), 162 – 178 (1984a).

Published

2023-05-24

How to Cite

[1]
Prof. Dr. Khalid A. Joudi, “COMPARISON OF COOLING LOAD CALCULATION METHODS BY”, jfath, vol. 9, no. 3, May 2023.